| dc.description.abstract | Grounding system design ensures safety compliance for transmission lines under lightning
conditions. In this regard, over time, efforts have been made to seek new techniques to
improve the transient response of grounding, mainly for high resistivity soils. In this
sense, one of the long-known techniques is the use of low resistivity materials around the
grounding electrodes, such as bentonite and concrete. However, despite the elapsed time,
few works in the literature carry out an in-depth study on the characterization of the
transient response of concrete-encased groundings; which would have special importance
in the evaluation of them for use in transmission line tower grounding. Given the above, in
order to contribute to the state of the art, in this work, the transient response of concrete
encapsulated electrodes is investigated. For this purpose, simulations were performed using
the finite element method, considering a rigorous electromagnetic modeling. Concreteencapsulated groundings of the vertical electrode type (rod) with 3 and 30 m, as well as
horizontal electrode (counterpoise) with 15, 30, 45 and 60 m, were analyzed. First and
subsequent stroke impulsive current excitations were considered. The effect of frequency
dependence of soil parameters was taken into account. In addition, soils with low, medium
and high resistivities (300 Ω.m to 4000 Ω.m) were evaluated. Different lengths of concrete
casing were taken into account in order to verify situations of partial or total encapsulation.
For all these cases, the harmonic impedance (from 60 Hz to 4 MHz) was simulated, and
the respective ground potential rise and impulsive impedance were calculated. In total,
150 different groundings were evaluated, each subjected to two discharges, totaling 300
impulsive responses. The results indicate that the concreting of the electrode in high
resistivity soils produced average reductions in impulsive impedance of up to 40% for the
3 m vertical rod, considering first and subsequent stroke. For the horizontal electrodes,
the reduction in impulsive impedance in high resistivity soils was up to 22% for first
stroke, while for subsequent stroke the results varied considerably between 10% and 26%,
depending on the electrode length and soil resistivity. Furthermore, it was found that the
use of concrete in grounding reduces the effective length of the electrode. | pt_BR |
| dc.language | por | pt_BR |
| dc.publisher | Universidade Federal da Bahia | pt_BR |
| dc.rights | Acesso Aberto | pt_BR |
| dc.subject | Aterramento Encapsulado por Concreto | pt_BR |
| dc.subject | Dependência da Frequência dos Parâmetros do Solo | pt_BR |
| dc.subject | Descargas Atmosféricas | pt_BR |
| dc.subject | Linhas de Transmissão | pt_BR |
| dc.subject | Impedância impulsiva | pt_BR |
| dc.subject | Transitórios Eletromagnéticos | pt_BR |
| dc.subject.other | Concrete encased grounding | pt_BR |
| dc.subject.other | Frequency dependence of electric parameters of soil | pt_BR |
| dc.subject.other | Ground enhancing compound | pt_BR |
| dc.subject.other | Impulse Impedance | pt_BR |
| dc.subject.other | Lightning response | pt_BR |
| dc.subject.other | Transmission line tower footing | pt_BR |
| dc.title | Avaliação da resposta transitória de aterramentos encapsulados por concreto | pt_BR |
| dc.title.alternative | Evaluation of the transient response of concrete-encased grounding | pt_BR |
| dc.type | Tese | pt_BR |
| dc.contributor.referees | Piantini, Alexandre | - |
| dc.publisher.program | Programa de Pós-Graduação em Engenharia Elétrica (PPGEE) | pt_BR |
| dc.publisher.initials | UFBA | pt_BR |
| dc.publisher.country | Brasil | pt_BR |
| dc.subject.cnpq | CNPQ::ENGENHARIAS::ENGENHARIA ELETRICA::SISTEMAS ELETRICOS DE POTENCIA::TRANSMISSAO DA ENERGIA ELETRICA, DISTRIBUICAO DA ENERGIA ELETRICA | pt_BR |
| dc.contributor.advisor1 | Moreira, Fernando Augusto | - |
| dc.contributor.advisor1ID | https://orcid.org/0000-0002-9565-9750 | pt_BR |
| dc.contributor.advisor1Lattes | http://lattes.cnpq.br/8068628216980918 | pt_BR |
| dc.contributor.advisor-co1 | Ferreira, Tarso Vilela | - |
| dc.contributor.advisor-co1ID | https://orcid.org/0000-0002-3852-8586 | pt_BR |
| dc.contributor.advisor-co1Lattes | http://lattes.cnpq.br/9395719025602516 | pt_BR |
| dc.contributor.referee1 | Moreira, Fernando Augusto | - |
| dc.contributor.referee1ID | https://orcid.org/0000-0002-9565-9750 | pt_BR |
| dc.contributor.referee1Lattes | http://lattes.cnpq.br/8068628216980918 | pt_BR |
| dc.contributor.referee2 | Ferreira, Tarso Vilela | - |
| dc.contributor.referee3 | Vasconcellos, Felipe Mendes de | - |
| dc.contributor.referee4 | Esquerre, Vitaly Félix Rodriguez | - |
| dc.contributor.referee5 | Lima, Antônio Carlos Siqueira de | - |
| dc.creator.ID | https://orcid.org/0000-0002-7191-5828 | pt_BR |
| dc.creator.Lattes | http://lattes.cnpq.br/7603022844978260 | pt_BR |
| dc.description.resumo | O correto dimensionamento do sistema de aterramento garante confiabilidade e segurança
no funcionamento das linhas de transmissão sob condições de descargas atmosféricas.
Quanto a isso, ao longo do tempo, esforços têm sido realizados buscando-se novas técnicas
para aprimoramento da resposta transitória dos aterramentos, principalmente para solos
de alta resistividade. Nesse sentido, uma das técnicas há muito conhecida é a utilização
de materiais de baixa resistividade ao redor dos eletrodos de aterramentos, tais como
a bentonita e o concreto. No entanto, apesar do tempo decorrido, poucos trabalhos na
literatura realizam um estudo aprofundado sobre a caracterização da resposta transitória
de aterramentos encapsulados por concreto, o que teria especial importância na avaliação
dos mesmos para uso em aterramentos de torres de linhas de transmissão. Diante do
exposto, e visando contribuir com o estado da arte, neste trabalho, a resposta transitória de
eletrodos de aterramento encapsulados por concreto é investigada. Para isso, realizaram-se
simulações através do método dos elementos finitos, considerando uma rigorosa modelagem
eletromagnética. Foram analisados aterramentos encapsulados por concreto do tipo eletrodo
vertical (haste) com 3 e 30 m, assim como de eletrodo horizontal (contrapeso) com 15,
30, 45 e 60 m. Consideraram-se excitações de correntes impulsivas de primeira descarga e
descarga subsequente. O efeito da dependência da frequência dos parâmetros do solo foi
considerado. Além disso, solos com resistividades baixa, média e alta (300 Ω.m a 4000 Ω.m)
foram avaliados. Diferentes comprimentos de revestimento de concreto foram levados em
consideração, a fim de verificar situações de encapsulamento parcial ou total. Para todos
esses casos, a impedância harmônica (de 60 Hz a 4 MHz) foi simulada, sendo calculadas
a respectiva elevação de potencial no aterramento e a impedância impulsiva. Ao todo,
foram avaliados 150 aterramentos diferentes, sendo cada um submetido a duas descargas,
totalizando 300 respostas impulsivas. Os resultados indicam que a concretagem do eletrodo,
em solos de média e alta resistividade produziu reduções médias na impedância impulsiva
de até 40%, para a haste vertical com 3 m, considerando primeira descarga e subsequente.
Já para os eletrodos horizontais, a redução na impedância impulsiva, em solos de média e
alta resistividade, foi de até 22%, para primeira descarga, enquanto que para descarga
subsequente os resultados variaram consideravelmente entre 10% a 26%, a depender do
comprimento do eletrodo e da resistividade do solo. Além disso, constatou-se que o uso de
concreto no aterramento reduz o comprimento efetivo do eletrodo. | pt_BR |